Terms & Policies

Hall Effect Sensors

Vane Sensors

  Life-time Warranty No questions asked Replacement / Refund

Consult us about our Best Price Guarantee!

 

Hall Current Sensor HIEM-DC-1000EKC/S

Print Friendly, PDF & Email

For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).

Datasheet PDF

Electrical Data

TYPE DC- 100EKC/S DC- 300EKC/S DC- 600EKC/S DC- 800EKC/S DC- 1000EKC/S
parameter sign
Primary nominal (r.m.s. current) IPN 100A 300A 600A 800A 1000A
Primary current measuring range IP 0~ 200A 0~ 600A 0~ 1200A 0~ 1600A 0~ 1500A
Secondary nominal RMS current ISN 12±8mA or 4~20mA
Supply voltage VC ±15V±1% or 24V±1%
Zero offset current @IPN =0, TA = 25°C I0 ±0.16mA
Thermal drift of offset current @IPN =0 IOT ±0.01mA/°C ±0.005mA/°C
Linearity of VSN at IPN =F.S εL ±1%F.S
Response time Tr <7μs
Ambient operating temperature Ta -10~+70°C      E:-40~+85°C
Ambient storage temperature Ts -40~+85°C        E:-55~+125°C

Dimension (mm)

Features

  1. Closed loop (compensated) multirange current sensor using the Hall effect
  2. Small size and space saving
  3. Very low temperature drift
  4. Wide frequency bandwidth
  5. High immunity to external interference

Applications

  1. AC variable speed drives and serve motor drives
  2. Uninterruptible Power Supplies (UPS)
  3. Battery supplied applications
  4. Power supplies for welding

Pin Identification

1:+15V 2:void 3:VOUT 4:GND