Terms & Policies

Hall Effect Sensors

Vane Sensors

  Life-time Warranty No questions asked Replacement / Refund

Consult us about our Best Price Guarantee!

 

Hall Current Sensor HIEM-DC-300LBK

Print Friendly, PDF & Email

For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).

Datasheet PDF

Electrical Data

TYPE DC- 50LBK DC- 100LBK DC- 200LBK DC- 300LBK
parameter sign
Primary nominal (r.m.s. current) IPN 50A 100A 200A 300A
Primary current measuring range IP 0~ ±150A 0~ ±300A 0~ ±400A 0~ ±500A
Secondary nominal RMS voltage VSN 4V±1%
Supply voltage VC ±15V DC ±5%
Zero offset voltage @IPN =0, TA = 25°C   V0   <±30mV
Thermal drift of offset voltage @IPN =0 VOT ±2.0mV/° C within±1mV/°C
Linearity of VSN  at IPN =F.S εL ±1% of VSN    at IPN    =F.S
Response time Tr 5μs Type    7μs max
R.m.s.  voltage for AC isolation test Vd 2.5KV/50 or 60Hz/1min
Ambientoperating temperature Ta -10~+80°C      E:-40~+85°C
Ambient storage temperature Ts -15~+85°C        E:-45~+105°C

Dimension (mm)

Features

  1. Opened loop (compensated) multirange current sensor using the Hall effect
  2. Flexible way of installment
  3. Small size and space saving
  4. Compact design for PCB mounting
  5. No insert losses

Applications

  1. AC variable speed drives and serve motor drives
  2. Uninterruptible Power Supplies (UPS)
  3. Battery supplied applications
  4. Power supplies for welding

Pin Identification

1:15V 2:-15V 3:VOUT 4:0V 5:void GIN:range adjustmeng OFS:zero adjustment