Hall Current Sensor HIEM-DC-600LT

Print Friendly, PDF & Email

For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).

Datasheet PDF

Electrical Data

TYPE DC- 100LT DC- 200LT DC- 300LT DC- 400LT DC- 500LT DC- 600LT
parameter sign
Primary nominal(r.m.s. current) IPN 100A 200A 300A 400A 500A 600A
Primary current measuring range IP 0~ ±300A 0~ ±600A 0~ ±900A 0~ ±900A 0~ ±1200A 0~ ±1200A
Secondary nominal RMS voltage VSN 4V±1% at IPN (RL =10 kΩ)
Supply voltage VC ±15V DC ±5%
Zero offset voltage @IPN =0, TA = 25°C   V0   ±30mV
Thermal drift of offset voltage @IPN =0   VOT   within±1mV/°C
Linearity of VSN at IPN =F.S εL ±1% of VSN at IPN =F.S
Response time Tr 7μs max
R.m.s. voltage for AC isolation test Vd 2.5KV/50 or 60Hz/1min
Ambient operating temperature Ta -10~+80°C      E:-40~+85°C
Ambient storage temperature Ts -15~+85°C        E:-45~+105°C

Dimension (mm)

Features

  1. Opened loop (compensated) multirange current sensor using the Hall effect
  2. Flexible way of installment
  3. Low power consumption
  4. No insert losses
  5. High immunity to external interference

Applications

  1. AC variable speed drives and serve motor drives
  2. Uninterruptible Power Supplies (UPS)
  3. Battery supplied applications
  4. Power supplies for welding

Pin Identification

1:+15V 2:-15V 3:Output 4:0V