Terms & Policies

Hall Effect Sensors

Vane Sensors

  Life-time Warranty No questions asked Replacement / Refund

Consult us about our Best Price Guarantee!

 

Hall Current Sensor HIEM-DC-800NC

Electrical Data

TYPE DC- 100NC DC- 200NC DC- 300NC DC- 400NC DC- 600NC DC- 800NC
parameter sign
Primary nominal (r.m.s. current) IPN 100A 200A 300A 400A 600A 800A
Primary current measuring range IP 0~±300A 0~±600A 0~±900A 0~±1200A 0~±1800A 0~±1800A
Secondary nominal RMS voltage VSN 4V±1% at IPN      (RL    =10 kΩ)
Supply voltage VC ±15V DC ±5%
Zero offset voltage @IPN =0, TA = 25°C   V0   within±30mV
Thermal  drift  of offset voltage @IPN =0 VOT within±1mV/°C
Linearity  of VSN at IPN =F.S εL ±1% of VSN at IPN =F.S
Response time Tr 7μs max
R.m.s. voltage for AC isolation test Vd 2.5KV/50 or 60Hz/1min
Ambient operating temperature Ta -10~+80°C      E:-40~+85°C
Ambient storage temperature Ts -15~+85°C        E:-45~+105°C

Dimension (mm)

Features

  1. Opened loop (compensated) multirange current sensor using the Hall effect
  2. Small size and space saving
  3. Low power consumption
  4. High immunity to external interference
   

Applications

  1. AC variable speed drives and serve motor drives
  2. Uninterruptible Power Supplies (UPS)
  3. Battery supplied applications
  4. Power supplies for welding applications

Pin Identification

1:+15V 2:-15V 3:Output 4:0V